Random PLC Resets and Faults: Finding 24 V Supply Dips

Faults appear with no pattern in the program, but always near a big load switching. The 24 V supply is the suspect — here is how to catch it.

The symptom

The PLC occasionally restarts, a remote IO station drops out, sensors flicker, or the HMI reboots. The program and network look fine, and the faults seem random.

Many of these "random" faults come from a 24 VDC supply that dips for a few milliseconds, which is too short for a multimeter to show.

Step 1: add up the load

List everything on the supply: CPU, IO modules, sensors, valve coils, HMI, relays, signal lamps and switches. Use the datasheet currents. Then add inrush, because HMIs, valve islands and capacitive loads draw several times their running current at switch-on.

A 5 A supply carrying 4.6 A continuous has no headroom left when four valves fire together.

Step 2: measure the right way

A multimeter averages its reading and misses short dips. Use one of these instead:

  • A multimeter with MIN/MAX recording on DC volts, left connected for a shift.
  • An oscilloscope or a power-quality logger triggered on a fall below, for example, 21 V.
  • Measure at the load end (the PLC terminals), not only at the supply output.

    Step 3: voltage drop in the wiring

    Long, thin cables drop voltage under load. 1.5 A through 50 m of 0.75 mm² cable (100 m round trip) drops roughly 3.5 V. A field device that sees 20.5 V may keep working until something else on the same circuit draws current.

    Step 4: check the primary side

    If the 24 V supply itself dips when a large motor starts direct-on-line, the mains feeding the power supply is sagging. Check that the supply's input range covers the sag, or feed it from a stiffer source.

    Fixes

    Split the loads. Give actuators such as valves and relays their own supply (or their own electronic circuit breaker channel), and keep a clean one for the CPU and IO electronics.

    Size with margin, typically 20–30% headroom over the calculated peak. Supplies with a power boost, or buffer modules (capacitor or battery), ride through short dips.

    Fit electronic circuit breakers per branch, so a short on one sensor cable does not take the whole supply down. On long runs, use the correct wire cross-section or put distributed supplies out in the field.

    Confirm the fix

    Re-run the MIN/MAX measurement over the same production period. The minimum voltage should stay well above the lowest input voltage the devices accept. The hardware chapter on signals lists the input thresholds.

    Frequently asked questions

    Can a 24 V power supply cause random PLC faults?

    Yes. Short voltage dips under inrush or overload can reset CPUs, drop IO stations and make inputs flicker without any fault in the program.

    How do I find short 24 V dips?

    Use a multimeter with MIN/MAX recording or an oscilloscope triggered on low voltage, measured at the load terminals over a full production period.