Troubleshooting
HMI Shows #### or "Communication Lost": Finding the Broken Link
Every value on the screen turned into ####. Is it the network, the PLC, or the HMI project? A short sequence separates the three.
The symptom
The operator panel shows #### (or *, or red crosses) in all value fields, or a banner such as Connection to PLC lost. Sometimes only one screen or a few tags are affected.
All values or some values?
This single observation halves the search.
When all values are lost
When some values are lost
Intermittent loss
If the banner appears and disappears, check for network load (a broadcast storm or a looping cable), a duplicate IP, and the HMI update rate. Polling hundreds of tags at 100 ms when 1 s is enough loads both PLC and network.
Prevent the next one
Show a clear communication-status indicator on every screen, and keep PLC and HMI projects versioned together so a download of one prompts a check of the other. See the HMI programming guide.
Frequently asked questions
Why does my HMI show ####?
Either the HMI lost connection to the PLC (all values affected) or specific tags are invalid or too long for their display field (some values affected).
Why did the HMI stop working after a PLC download?
Renamed or deleted variables, changed data types or a changed PLC IP address break HMI tags. Recompile and download the HMI project to match.