Analog Input Reads 0 or Overrange: Troubleshooting a 4–20 mA Loop
Your transmitter display says 3.2 bar but the PLC shows 0 or a wire-break alarm. Here is the measuring order that finds the cause in minutes.
The symptom
The local display on a pressure transmitter reads 3.2 bar, but the PLC tag shows 0, -32768, 32767, or the card raises a wire break / underrange diagnostic. Operators blame the program. In most cases the program is fine — the loop is not delivering current to the card.
Work through the checks below in order. Each one splits the problem in half, so you never guess.
Step 1 — Read the raw value, not the scaled tag
Open the online view of the raw input word (for example %IW64 on a Siemens S7-1500 or the .Data member on a Rockwell 1769-IF4). Note the number:
| Raw value (Siemens style) | What the card sees |
|---|---|
| 0 | About 4 mA — the zero of the range |
| 27648 | About 20 mA — full scale |
| 32767 / 7FFF hex | Overrange or wire break (above ~22.8 mA or open) |
| -32768 / 8000 hex | Underrange / wire break (below ~1.2 mA) |
Step 2 — Measure the loop current, series not parallel
Put a multimeter on the mA range in series with the loop, or use a clamp-on mA meter if you cannot open the circuit. Many transmitters have TEST terminals across a diode, which let you read current without breaking the loop.
Step 3 — Who powers the loop?
This is the single most common commissioning mistake. A 2-wire transmitter needs 24 V from somewhere, and only one place:
If both the card and an external supply drive the loop, or neither does, you get 0 mA or a damaged channel. Check the terminal diagram for the exact card part number, not a similar one.
Step 4 — Check the voltage budget
Measure the voltage across the transmitter terminals with the loop running. A typical transmitter needs at least 10.5–12 V to operate. Add up everything in the loop at 20 mA: card input resistance (often 250 Ω = 5 V), any barrier (Ex isolators can drop 7–8 V), indicators and long cable. If the remaining voltage is below the minimum, the reading collapses as the process rises — it looks fine at low pressure and fails near full scale.
Step 5 — Confirm channel configuration
Open the hardware configuration. Confirm the channel type (current 2-wire, current 4-wire, voltage), the range (4–20 mA, not 0–20 mA), and that diagnostics such as wire-break are enabled where you expect them. A channel set to voltage with a current signal will read nearly zero.
Step 6 — Check the scaling arithmetic
With raw 0–27648 mapped to 0–10 bar:
Pressure := (REAL(Raw) / 27648.0) * 10.0;
Common errors: integer division (Raw / 27648 gives 0 for every value below full scale), the wrong raw span (Rockwell cards are configured per channel and may use engineering units directly), and forgetting a 4 mA offset when the raw span starts at a non-zero count.
What to remember
Measure before you edit code. Raw value, then loop current, then loop power, then configuration, then scaling — five checks that locate almost every analog fault. You can practise the scaling step with the analog scaling calculator and read more about signals in the hardware chapter on signals.
Frequently asked questions
Why does my PLC show 32767 on an analog input?
On most Siemens-style cards 32767 (7FFF hex) means overrange or an open circuit. Measure the loop current: 0 mA means an open or unpowered loop, above 22 mA means the transmitter or loop is overdriven.
What does 3.6 mA mean on a 4–20 mA loop?
Under NAMUR NE43 a current below 3.8 mA is a transmitter failure signal. Check the transmitter diagnostics before changing anything in the PLC.